Medium voltage power capacitors

For more details please open our catalogue: Power factor correction.pdf
Application

The capacitors are designed for power factor correction and harmonics filtration at medium voltage. They are all-film dielectric – polypropylene foil impregnated with an environmentally friendly, non-toxic biodegradable insulating oil. There is the aluminium foil as the electrodes. This construction assures minimal looses of the capacitors. Three-phase units are in star – Y connection, single-phase units are in I connection. The capacitors have internal discharge resistors.

Installation instruction
Technical data
Rated voltage:   UN   Three-phase 1-24 kV 25 … 800 kvar
Single-phase 1-12 kV 25 … 700 kvar
Frequency:   fN   50/60 Hz
Standards:       IEC 60871-1: 1997 EN 60871-1: 1997 EN ČSN 60871-1; 1999
IEC 60871-4: 1997 EN 60871-4: 1997 EN ČSN 60871-4; 1999
Max overvoltage:   Umax  

UN + 10 % (up to 8 hours daily)
UN + 15 % (up to 30 minutes daily)
UN + 20 % (up to 5 minutes)
UN + 30 % (up to 1 minute)

Overcurrent (according to above standards):   IS   1,3 * IN
Capacitance tolerance:       -5 / +10 %
Test voltage, terminal/terminal:   UTT   2,15 * UN, AC, 10 s or 4,3 * UN DC, 10 s
Test voltage, terminal / case:   UTC   According to relevant IEC standard for 10 s
Inrush current:       Max 200 x IN
Dielectric losses:   tan δ   cca 0,07 W/kvar
Statistical life expectancy:       > 100 000 hours
Degree of protection:       IP 00, on request IP 42, indoor and outdoor
Ambient temperature category:       -40 °C / D  - maximum is 50 °C
                 - highest mean over any period of 24 h is 40 °C
                 - highest mean over any period of 1 year is 30 °C
Cooling:       naturally air cooled
Permissible relative humidity:       IP00-max. 95 %, IP42-max. 95 %
Max above sea level:       1 000 m above sea level
Mounting position:       vertical
Mounting:       Side brackets, bottom brackets
Case:       Stainless-steel, for indoor/outdoor installation
Dielectric:       All-film
Impregnant:       JARYLEC (environmentally friendly, non toxic, non PCB)
Discharge resistors:       Included -  75 V, 10 minute

Technical details

Installation instruction
  • Impregnant is free from PCB and is completely non-toxic. It is very stable over a wide operating temperature range
  • All three-phase and single-phase units are in dead case
  • Single-phase units are available with two bushings or connected with a single bushing and live case
  • Low voltage pressure sensor 230 V, 50 Hz available
  • Terminal cover IP42 available
  • Stainless steel case, paint finish. For indoor/outdoor installation
  • Max torque – hollow studs M12 - 10 Nm
  • Max torque - earth connection M10 - 7 Nm
     

ZEZ SILKO, s.r.o., Pod Černým lesem 683, 564 22 Žamberk, Czech Republic
E-mail: zez@zez-silko.cz, Http://www.zez-silko.cz, Tel: +420 465 673 111, Fax: +420 465 612 319